Product Catalogue
Temperature Controller KT-210
Home >> Prodcut Catalogue >> Controller for Refrigeration
Temperature Controller KT-210 | |
Brand Name: | Neutral or KingTill |
Brief Info: | Two relays, Sensor: NTC, 2 sensors, 2m(L) |
Product Description
Temperature Controller KT-210
Function:
Temperature and Control/ Manual, automatic defrost by electric heater
Time、temperature setting to end defrosting/ Value Storing / /Parameter Locking
Technical Parameter:
1. Power supply: 230V AC
2. Temp. sensor: NTC, 2 sensors (for cold room temp.&defrost control), 2m(L)
3. Temp. Measuring range: -45℃ ~ 66℃(-45℉ ~ 150℉) Accuracy: ±1℃(±2℉)
4. Temp. controlling range: -45℃ ~ 45℃(-45℉ ~ 120℉) Default : 0℃(±32℉)
5. Dimension: 77(Length) ×35(Width) × 60(Depth) mm
Mounting Size: 71(Length) × 29(Width) mm
6. Operation environment:
Temp.: -10℃ ~ 60℃, Relative Humidity: 20%~90% (No condensing)
7. Output contact capacity:
Compressor: 16A/250VAC
Defrost: 10A/250VAC
Menu:
Parameter | Function | Set range | Default |
E1 | Lower set-point limit | -45℃/45℉~Set temp. | -35℃/-31℉ |
E2 | Higher set-point limit | Set temp.~45℃/120℉ | 20℃/68℉ |
E3 | Temp. Return Difference | 1~10℃/ 1~18℉ | 4℃/7℉ |
E4 | Comp.start delay time | 0~10Min | 2Min |
E5 | Room Temp. Calibration | -20~20℃/-36~36℉ | 0 |
E6 | Offset on evap.Temp. | -20~20℃/-36~36℉ | 0 |
F1 | Defrost Time | 1~60Min | 20Min |
F2 | Defrost Cycle | 0~24Hr | 6Hr |
F3 | Defrost termination temp. | 0~20℃/ 32~68℉ | 8℃/46℉ |
F4 | Display during defrost |
0=Normal display 1=Last value before defrost |
0 |
F5 | Fan operating function |
0=Parallel with comp. 1=Continuous running except defrost |
0 |
C1 | Temperature unit | ℃=Celsius ℉=Fahrenheit | ℃ |